Description
N 525D11• 2 DALI outputs with DALI-2 certification• Control capacity for up to 20 DALI-ECGs per DALI output• DALI output voltage of 19 V, short circuit resistant• Integrated power supply with input voltage AC 110-240 V, 50-60 Hz or DC 120-240 V for powering the gateway electronics and DALI output• LED display for displaying operation mode and the following failure messages: Illuminant defective, DALI incorrect voltage, DALI short circuit, no ECG found• One pair of push buttons for switching On/Off and dimming of all connected DALI ECG• Button on the device front for deactivation of the direct mode operation and LED to indicate activation direct mode operation• Building site function that provides ex-factory enables switching the building site lighting on and off via bus wall switches and actuators, even if these devices have not yet been commissioned with the Engineering Tool Software (ETS)• Housing: plastic, N-system• DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715• Type of protection: IP 20• Max. width 4 TE (1 TE = 18 mm)
Documents Techniques
- 📄 A6V11914230 Switch- dimming actuator N 525D11 en.pdf
- 📄 A6V15245618 UL Online Certifications Directory 5WG1..-1.. de.pdf
- 📄 A6V14018712 EU Declaration of Conformity Switch- dimming actua de.pdf
- 📄 A6V14019344 Supplier s declaration of conformity N 525D11 en.pdf
- 📄 A6V14020115 UK Declaration of Conformity N 525D11 en.pdf
- 📄 A6V12563261 EPD Type II with LCA – KNX Building Control – 5WG1 en.pdf
- 📄 A6V14019363 017 EPD Environmental Product Declaration 5WG1 5W en.pdf
- 📄 A6V14019565 Environmental Product Declaration N 525D11 en.pdf